TM 11574A-OI
3-32
Figure 3-13. DPRV Replacement Value Chart.
NOTE
This test should not be run below 30 F (-1.1 C) or above 120 F (49 C). If the actual
differential pressure is close to the replacement differential pressure, it is recommended
that the readings be taken several times at two minutes intervals.
If valve cap is found to be leaking it may be replaced using cap & O-ring (Carrier Part Number 40-
50024-00).
(17) Autotransformer
(a) If the Autotransformer unit does not start, check the following:
1
Make sure the 460 VAC (yellow) power cable is plugged into the receptacle (Figure
TBA, Item 3) and locked in place.
2
Make sure that circuit breakers CB-1 and CB-2 are in the “ON” position. If the circuit
breakers do not hold in, check voltage supply.
3
There is no internal protector for this transformer design; therefore, no checking of
the internal protector is required.
4
Using a voltmeter and with the primary supply circuit ON, check the primary (input)
voltage (460 VAC). Next, check the secondary (output) voltage (230 VAC). The
transformer is defective if output voltage is not available.